3: I
NSTALLATION
AND
W
IRING
3-46
FC6A S
ERIES
MICROS
MART
U
SER
’
S
M
ANUAL
FC9Y-B1722
■
Expansion Interface Remote Master Module, HMI Module, and Cartridge
*1 Used when removing the wires.
*2 Spring clamp type.
Crimping Tool
The following crimping tool can be used with FC6A Series MICROSmart.
Module Type
Expansion Interface
Remote Master Module
HMI Module
Cartridges
Wire Type
UL1007
UL2464
Equivalent
UL1015
Equivalent
UL1007
UL2464
Equivalent
UL1015
Equivalent
UL1007
UL2464
Equivalent
UL1015
Equivalent
Stripping length (mm)
7
7
5
Wire thickness (mm
2
)
0.14 to 2.5
0.14 to 2.5
0.14 to 1.50
Wire
gauge
AWG 24
1-wire
usage
AI 0,25- 6 (3203040)
―
―
Yes
―
Yes
―
AI 0,25- 8 (3203037)
Yes
―
Yes
―
―
―
AI 0,25-10 (3241128)
―
―
―
―
―
―
AWG22
1-wire
usage
AI 0,34- 6 (3203053)
―
―
Yes
―
Yes
―
AI 0,34- 8 (3203066)
Yes
―
Yes
―
―
―
AI 0,34-10 (3241129)
―
―
―
―
―
―
AWG20
1-wire
usage
AI 0,5- 6 (3200687)
―
―
Yes
―
Yes
―
AI 0,5- 8 (3200014)
Yes
―
Yes
―
―
―
AI 0,5- 8 GB (1208966)
―
Yes
―
Yes
―
―
AI 0,5-10 (3201275)
―
―
―
―
―
―
AI 0,5-10 GB (3203150)
―
―
―
―
―
―
2-wire
usage
AI-TWIN 2 x 0,5-8
(3200933)
Yes
―
Yes
―
―
―
AI-TWIN 2 x 0,5-10
(3203309)
―
―
―
―
―
―
AWG18
1-wire
usage
AI 0,75- 6 (3200690)
―
―
Yes
―
―
―
AI 0,75- 8 (3200519)
Yes
―
Yes
―
―
―
AI 0,75-10 (3201288)
―
―
―
―
―
―
AI 1-8 (3200030)
Yes
―
―
Yes
―
―
AI 1-10 (3200182)
―
―
―
―
―
―
2-wire
usage
AI-TWIN 2 x 0,75-8
(3200807)
Yes
―
Yes
―
―
―
AI-TWIN 2 x 0,75-10
(3200975)
―
―
―
―
―
―
AWG16
1-wire
usage
AI 1,5- 6 (3200755)
―
―
Yes
Yes
―
―
AI 1,5- 8 (3200043)
Yes
Yes
―
Yes
―
―
AI 1,5-10 (3200195)
―
―
―
―
―
―
2-wire
usage
AI-TWIN 2 x 1,5-8
(3200823)
Yes
―
―
―
―
―
Screwdriver
SZS 0.4×2.5 (1205037)
―
―
Yes
SZS 0.6×3.5 (1205053)
―
Yes
―
SZF 1-0,6×3,5 (1204517)
Yes
―
―
Tightening torque (N)
0.51
0.22 to 0.25
Tool Name
Phoenix Contact Model Number (order number)
Crimping tool
CRIMPFOX 6 (1212034)
Do not touch live terminals. There is a risk of electric shock.
When powered, the terminals that are connected to external devices may become hot. Do not touch the terminals
immediately after turning the power off.
Do not touch the power supply terminals immediately after turning the power off. There is a risk of electric shock.
Insert the wire all the way to the tip of the ferrule and crimp it.
When connecting stranded wire or multiple wires to a terminal block, use a ferrule. Otherwise there is a risk of wires
becoming disconnected.
When using single wires, you do not need to use ferrules.
Single wire assumes the use of one wire. Do not attach two or more wires to the one connector hole.
Caution
Summary of Contents for MICROSmart FC6A Series
Page 1: ...B 1722 8 FC6A SERIES User s Manual...
Page 12: ...TABLE OF CONTENTS Preface 11 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 182: ...2 PRODUCT SPECIFICATIONS 2 152 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 434: ...8 INSTRUCTIONS REFERENCE 8 18 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 520: ...11 SD MEMORY CARD 11 54 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 554: ...13 TROUBLESHOOTING 13 26 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 567: ...FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722 A 13 APPENDIX ASCII Character Code Table...