Internal Relay ‘Keep’ Designation (M0000 to M7997)
Internal Relay ‘Keep’ Designation (All-in-One CPU module: M10000 to M17497, Plus CPU module: M10000
to M21247)
Shift Register ‘Keep’ Designation
Counter ‘Clear’ Designation
Data Register ‘Clear’ Designation (D0000 to D7999)
Data Register ‘Clear’ Designation (All-in-One CPU module: D10000 to D55999, Plus CPU module: D10000 to
D61999)
Notes:
When the FC6A Series MICROSmart has lost its keep data, the
Run/Stop Selection at Memory Backup Error
setting has priority over the
Run/Stop Selection at Power Up
setting.
Relays and registers specified as
Clear Al
l or
Clear Specified Range
are cleared when the FC6A Series MICROSmart starts operation. The
values while the power is off are retained until the power is turned on and operation is started.
Keep/clear settings cannot be configured for special data registers. They operate the same as
Keep All
.
Keep/clear settings cannot be configured for special internal relays. For operation when the power is shut off and when stopped, see
"Devices" - "Special Internal Relay" on page 6-4.
Clear All:
Clears the internal relays (M0000 to M7997) when the FC6A Series MICROSmart starts operation.
Keep All:
Keeps the status of the internal relays (M0000 to M7997) while the FC6A Series MICROSmart power is off.
Keep Specified Range:
Keeps the status of the internal relays in the specified range while the FC6A Series MICROSmart power is off.
When a range of M50 through M100 is designated as shown in the example above, M50 through M100 are keep
types, M0 through M47 and M101 through M7997 are clear types.
Clear All:
Clears the internal relays (All-in-One CPU module: M10000 to M17497, Plus CPU module: M10000 to M21247)
when the FC6A Series MICROSmart starts operation.
Keep All:
Keeps the status of the internal relays (All-in-One CPU module: M10000 to M17497, Plus CPU module: M10000 to
M21247) while the FC6A Series MICROSmart power is off.
Keep Specified Range:
Keeps the status of the internal relays in the specified range while the FC6A Series MICROSmart power is off.
Clear All:
All shift register bit statuses are cleared at startup (default).
Keep All:
All shift register bit statuses are maintained at startup.
Keep Specified Range:
A specified range of shift register bits are maintained at startup. Enter the start “keep” number in the left field
and the end “keep” number in the right field. The start “keep” number must be smaller than or equal to the end
“keep” number.
Clear All:
All counter current values are cleared at startup.
Keep All:
Keeps all counter current values while the FC6A Series MICROSmart power is off.
Clear Specified Range:
A specified range of counter current values are cleared at startup. Enter the start “clear” number in the left field
and the end “clear” number in the right field. The start “clear” number must be smaller than or equal to the end
“clear” number.
Clear All:
Clears the values of the data registers (D0000 to D7999) when the FC6A Series MICROSmart starts operation.
Keep All:
Keeps the values of the data registers (D0000 to D7999) while the FC6A Series MICROSmart power is off.
Clear Specified Range:
A specified range of data register values are cleared at startup. Enter the start “clear” number in the left field and
the end “clear” number in the right field. The start “clear” number must be smaller than or equal to the end
“clear” number.
Clear All:
Clears the values of the data registers (All-in-One CPU module: D10000 to D55999, Plus CPU module: D10000 to
D61999) when the FC6A Series MICROSmart starts operation.
Keep All:
Keeps the values of the data registers (All-in-One CPU module: D10000 to D55999, Plus CPU module: D10000 to
D61999) while the FC6A Series MICROSmart power is off.
Clear Specified Range:
A specified range of data register values are cleared at startup. Enter the start “clear” number in the left field and
the end “clear” number in the right field. The start “clear” number must be smaller than or equal to the end
“clear” number.
End Keep Number (
Start Keep Number)
Start Keep Number
Summary of Contents for MICROSmart FC6A Series
Page 1: ...B 1722 8 FC6A SERIES User s Manual...
Page 12: ...TABLE OF CONTENTS Preface 11 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 182: ...2 PRODUCT SPECIFICATIONS 2 152 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 434: ...8 INSTRUCTIONS REFERENCE 8 18 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 520: ...11 SD MEMORY CARD 11 54 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 554: ...13 TROUBLESHOOTING 13 26 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 567: ...FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722 A 13 APPENDIX ASCII Character Code Table...