FC6A S
ERIES
MICROS
MART
U
SER
’
S
M
ANUAL
FC9Y-B1722
5-25
5: F
UNCTIONS
AND
S
ETTINGS
Settings
■
Operation mode
For group 1 and group 5, you can select
Single-phase High-speed Counter
or
Two-phase High-speed Counter
.
Only
Single-phase High-speed Counter
can be selected for Group 2, Group 4, and Group 6.
The operation mode that can be selected for Group 3 depends on the type of FC6A Series MICROSmart.
Only
Single-phase High-speed Counter
can be selected for the All-in-One CPU module.
Single-phase High-speed
Counter
and
Two-phase High-speed Counter
can be selected for the Plus CPU module.
■
Counting mode (single-phase high-speed counter)
When the
Single-phase High-speed Counter
is specified for
Operation Mode
of Group 1 or Group 5,
Counting Mode
can
be selected as
Adding Counter
,
Up/Down Selection Reversible Counter
, or
Dual-Pulse Reversible Counter
.
Only
Adding Counter
can be selected for Group 2, Group 4, and Group 6 high-speed counters.
The counting mode that can be selected for Group 3 depends on the type of FC6A Series MICROSmart.
Only
Adding Counter
can be selected for the All-in-One CPU module.
Adding Counter
,
Up/Down Selection Reversible
Counter
, and
Dual-Pulse Reversible Counter
can be selected for the Plus CPU module.
Adding counter
The adding counter counts up with the rise in pulse input.
Up/down selection reversible counter
Up/down selection reversible counter can switch between addition and subtraction with the up/down selection input. When the
up/down selection input is on, the counter counts up with the rise in pulse input. When the up/down selection input is off, the
counter counts down with the rise in pulse input.
Dual-pulse reversible counter
This counter switches between the up count and the down count with pulse input (up) and pulse input (down) pulses. When a
pulse is input to pulse input (up), the counter counts up with the rise in the pulse. When a pulse is input to pulse input (down),
the counter counts down with the rise in pulse input.
Note:
When Group 1, Group 3 (Plus CPU module), or Group 5 is set to
Up/Down Selection Reversible Counter
,
Dual-Pulse Reversible
Counter
, or
Two-phase High-speed Counter
, Group 2, Group 4, or Group 6 has the same setting.
■
Counting mode (two-phase high-speed counter)
When the two-phase high-speed counter is specified for
Operation mode
for group 1, group 3 (Plus CPU module), or group 5, the
counting mode can be selected as
2-edge count
or
4-edge count
.
2-edge count
This counter counts at double the frequency of the input pulse.
This counter counts by the phase difference between the A-phase and B-phase pulse input. When the A-phase precedes the B-
phase, the counter counts up with the rise and fall of the B-phase. When the B-phase precedes the A-phase, the counter counts
down with the rise and fall of the B-phase.
4-edge count
This counter counts at quadruple the frequency of the input pulse.
This counter counts by the phase difference between the A-phase and B-phase pulse input. When the A-phase precedes the B-
phase, the counter counts up with the rise and fall of the A-phase and the B-phase. When the B-phase precedes the A-phase,
the counter counts down with the rise and fall of the A-phase and the B-phase.
■
Comparison action
The comparison action is a function that compares the high-speed counter's current value with a preset value (target value).
It can use either the comparison output or an interrupt program. However, the interrupt program can only be used when ladder
program is selected as the programming language.
When
Comparison Output
is selected, the specified external output is turned on when the current value and the preset value match.
When
Interrupt Program
is selected, the subroutine program with the specified label number is executed as the interrupt program when
the current value and the preset value match.
Overflow and underflow can also be used for the comparison conditions.
For details on the comparison actions, see "Comparison Actions" on page 5-21.
Summary of Contents for MICROSmart FC6A Series
Page 1: ...B 1722 8 FC6A SERIES User s Manual...
Page 12: ...TABLE OF CONTENTS Preface 11 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 182: ...2 PRODUCT SPECIFICATIONS 2 152 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 434: ...8 INSTRUCTIONS REFERENCE 8 18 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...