Program
M8120 (initialize pulse) is a special internal relay that turns on when the FC6A Series MICROSmart runs.
Note:
In this example, Z-phase reset input is not used.
Preset value 1=2,700
2,700 pulses
Perforation time: 0.5 seconds
Q2
M8031
M8031
M8032
M8030
M0000
M0000
M0000
M8120
Current value
Reset value 0
Comparison output Q2
M8120
SOTU
SOTD
D1-
D0004
REP
S1-
2700
MOV(D)
D1-
D8216
REP
S1-
0
MOV(D)
D1-
D0002
REP
S1-
1
MOV(W)
TIM
5
T000
1st scan
Store 2,700 in preset value 1 (D0004, D0005)
3rd scan
Detect the rising edge of M0000, turn on gate input (M8031)
2nd scan
Detect the falling edge of the initialize pulse, M0000 and M8032 turn on
Initialize the current value with the reset value in the END processing
after the 2nd scan is executed
Store 0 in the reset value (D8216, D8217)
Turn off gate input (M8031)
Turn off M0000
M8032 (reset input) is a special internal relay that stores the reset
value (D8216, D8217) in the current value (D8210, D8211).
When the current value becomes 2,700 pulses, comparison
output Q2 turns on
The timer starts and comparison output reset (M8030) turns on after
5 seconds
Store 1 in the next preset value number (D0002)
Summary of Contents for MICROSmart FC6A Series
Page 1: ...B 1722 8 FC6A SERIES User s Manual...
Page 12: ...TABLE OF CONTENTS Preface 11 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 182: ...2 PRODUCT SPECIFICATIONS 2 152 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 434: ...8 INSTRUCTIONS REFERENCE 8 18 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 520: ...11 SD MEMORY CARD 11 54 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 554: ...13 TROUBLESHOOTING 13 26 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 567: ...FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722 A 13 APPENDIX ASCII Character Code Table...