FC6A S
ERIES
MICROS
MART
U
SER
’
S
M
ANUAL
FC9Y-B1722
5-35
5: F
UNCTIONS
AND
S
ETTINGS
Catch Input
The catch input function is used to receive short pulses from sensor outputs regardless of the scan time. Input pulses shorter than one scan time
can be received. When using catch input, the on/off status according to the status of the external inputs during one scan is stored in the special
internal relays (M8153 to M8157, M8160) that correspond to each external input group, and those signals can be used as input conditions.
The
Function Area Settings
dialog box is used to designate inputs I0, I1, I3, I4, I6 and I7 as a catch input.
Normal input signals to input terminals are read when the END instruction is executed at the end of a scan.
Since these settings relate to the user program, the user program must be downloaded to the FC6A Series MICROSmart after
changing any of these settings.
Catch Input Specifications
Note:
Input filter settings have no effect on the catch inputs. For the input filter function, see "Input Filter" on page 5-42.
External Inputs
External inputs on the FC6A Series MICROSmart can be switched between and used as normal inputs, high-speed counters, catch
inputs, interrupt inputs, and frequency measurements. To use catch inputs, specify the corresponding group as
Catch Input
in
the
Function Area Settings
of WindLDR.
The status of external inputs that are assigned to catch inputs are stored in the following special internal relays by group (read-only).
All-in-One CPU module
*1 Can be used as a normal input.
*2 Read-only.
Plus CPU module
*1 Can be used as a normal input.
*2 Can be used only with the Plus 32-I/O type.
*3 Read-only.
Programming WindLDR
1.
From the WindLDR menu bar, select
Configuration
>
Input Configuration
.
The
Function Area Settings
dialog box for Input Configuration appears.
Minimum Turn ON Pulse Width
5 µs
Minimum Turn OFF Pulse Width
5 µs
Group
1
2
3
4
5
6
External Input
I2
I0
I1
I3
I4
I5
I6
I7
Catch Input
Yes
Yes
Yes
Yes
—
Yes
Yes
Special Internal Relay
—
M8153
M8154
M8155
M8156
—
M8157
M8160
Group
1
2
3
4
5
6
External Input
I2
I0
I1
I3
I4
I5
I6
I7
Catch Input
Yes
Yes
—
Yes
Yes
Yes
Yes
Special Internal Relay
—
M8153
M8154
—
M8155
M8156
—
M8157
M8160
Catch Input Rising/Falling
Edge Selection
Catch Input Rising Edge
Catch Input Falling Edge
Summary of Contents for MICROSmart FC6A Series
Page 1: ...B 1722 8 FC6A SERIES User s Manual...
Page 12: ...TABLE OF CONTENTS Preface 11 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 182: ...2 PRODUCT SPECIFICATIONS 2 152 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 434: ...8 INSTRUCTIONS REFERENCE 8 18 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 520: ...11 SD MEMORY CARD 11 54 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 554: ...13 TROUBLESHOOTING 13 26 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 567: ...FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722 A 13 APPENDIX ASCII Character Code Table...