LOGIC
5-330
Control start
This function confirms operation of the connected start input device. As shown in Fig.5-28, this
function is comprised of a functional input (I
n
) and a functional output (O
n
).
The start input (I
n
) ON operation is monitored to determine whether it is performed within the
designated control time (0.1 s to 5 s).
Fig. 5-28 Control start function circuit
Description of operation
The operation timing is described in Fig. 5-29.
I If the input turns ON within the designated control time (0.1 s to 5 s), the output turns ON until
the connected self-holding function or another trigger input turns ON. (The function output
turns OFF after the other trigger input turns ON.)
II If the input does not turn ON within the designated control time (0.1 s to 5 s) (If the function
input turns on before 0.1 s or after 5 s), the output does not turn ON.
I
n
O
n
Control time
:0.1s~5s
Ⅰ
Ⅱ
0.1s
5s
0.1s
5s
Control time
:0.1s~5s
ON
OFF
ON
OFF
Fig. 5-29 Operation timing of the control start function
I
n
O
n
Control
Start
Control
Summary of Contents for FS1A-C11S
Page 1: ...FS9Z B1218 FS1A C11S Safety Controller SafetyOne User s manual ...
Page 2: ......
Page 10: ......
Page 16: ...PRODUCT SPECIFICATIONS 2 4 Dimensions Detail of locking ring Locking ring ...
Page 38: ...INSTALLATION AND WIRING 3 8 ...
Page 48: ...BASIC OPERATIONS 4 10 ...
Page 78: ...LOGIC 5 30 ...
Page 90: ...LOGIC 5 42 ...
Page 102: ...LOGIC 5 54 ...
Page 116: ...LOGIC 5 68 ...
Page 154: ...LOGIC 5 106 ...
Page 231: ...LOGIC 5 183 Chapter 5 ...
Page 307: ...LOGIC 5 259 Chapter 5 ...
Page 319: ...LOGIC 5 271 Chapter 5 ...
Page 331: ...LOGIC 5 283 Chapter 5 ...
Page 386: ...LOGIC 5 338 ...