![IDEC FS1A-C11S User Manual Download Page 261](http://html.mh-extra.com/html/idec/fs1a-c11s/fs1a-c11s_user-manual_617376261.webp)
LOGIC
5-213
C
h
a
p
te
r 5
Warning
For connected control devices, refer to “SAFETY PRECAUTIONS”.
Safety check signals (pulses signals) are sent from the drive terminals (T0, T2 to T11) to diagnose
connected safety devices and input circuits. Safety check signals can not be used as a power supply
for connected devices.
Note. Solid state outputs, such as safety light curtains, can not be connected to safety inputs.
Note. Use safety inputs, as specified combinations, such as receive terminal (Xn) and drive terminal
(Tn). If the combinations are incorrect, SafetyOne does not work correctly.
Note. When SafetyOne is in Run state or Protection state, input states are monitored in all safety
inputs. For example, if input monitor error is detected in safety input 2 although AUTO mode is
selected, SafetyOne detects error and transits to Protection state.
Note. If there are unused safety inputs in safety input 2 through safety input 5, connect the unused
receive terminals (Xn) to the corresponding drive terminals (Tn). If they are not connected, the
SafetyOne does not turn ON the safety outputs.
●External device monitor inputs: X12 to X15 (T12 to T15)
External device monitor inputs are used to diagnose status of the devices connected to safety outputs.
Intended inputs
(Terminal names)
Target safety
outputs (Terminal
names)
Function
External device monitor input 1
(X12-T12)
Safety output 1-1
(Y0)
Function name
External device monitor input
External device monitor input 2
(X13-T13)
Safety output 1-2
(Y1)
Symbol
External Device
Monitor
EDM
External device monitor input 3
(X14-T14)
Safety output 2-1
(Y2)
Description of
operation
This function diagnoses the
status of devices connected to a
target safety output.
External device monitor input 4
(X15-T15)
Safety output 2-2
(Y3)
Detail
information
Logic functions (5-326)
Warning
Safety check signals (pulses signals) are sent from the drive terminals (T12 to T15) to diagnose
external devices and monitor circuits. Safety check signals can not be used as a power supply for
connected devices.
Note. If there are unused safety outputs, connect the intended external device monitor terminals (Xn)
to the corresponding drive terminals (Tn). If they are not connected, the SafetyOne detects an
input monitor error. As the result, the error LED displays a “1” and the unit changes to the
Protection state.
Summary of Contents for FS1A-C11S
Page 1: ...FS9Z B1218 FS1A C11S Safety Controller SafetyOne User s manual ...
Page 2: ......
Page 10: ......
Page 16: ...PRODUCT SPECIFICATIONS 2 4 Dimensions Detail of locking ring Locking ring ...
Page 38: ...INSTALLATION AND WIRING 3 8 ...
Page 48: ...BASIC OPERATIONS 4 10 ...
Page 78: ...LOGIC 5 30 ...
Page 90: ...LOGIC 5 42 ...
Page 102: ...LOGIC 5 54 ...
Page 116: ...LOGIC 5 68 ...
Page 154: ...LOGIC 5 106 ...
Page 231: ...LOGIC 5 183 Chapter 5 ...
Page 307: ...LOGIC 5 259 Chapter 5 ...
Page 319: ...LOGIC 5 271 Chapter 5 ...
Page 331: ...LOGIC 5 283 Chapter 5 ...
Page 386: ...LOGIC 5 338 ...