LOGIC
5-188
●External device monitor inputs: X14 and X15 (T14 and T15)
External device monitor inputs are used to diagnose status of the devices connected to safety outputs.
Intended inputs
(Terminal names)
Target safety
outputs
(Terminal
names)
Function
External device monitor input 1
(X14-T14)
Safety output 1
(Y0, Y1)
Function name
External device monitor input
External device monitor input 2
(X15-T15)
Safety output 2
(Y2, Y3)
Symbol
External Device
Monitor
EDM
Description of
operation
This function diagnoses the
status of devices connected to a
target safety output.
Detail information
Logic functions (5-326)
Warning
Safety check signals (pulses signals) are sent from the drive terminals (T14, T15) to diagnose external
devices and monitor circuits. Safety check signals can not be used as a power supply for connected
devices.
Note. If there are unused safety outputs, connect the intended external device monitor terminals (Xn)
to the corresponding drive terminals (Tn). If they are not connected, the SafetyOne detects an
input monitor error. As the result, the error LED displays a “1” and the unit changes to the
Protection state.
Summary of Contents for FS1A-C11S
Page 1: ...FS9Z B1218 FS1A C11S Safety Controller SafetyOne User s manual ...
Page 2: ......
Page 10: ......
Page 16: ...PRODUCT SPECIFICATIONS 2 4 Dimensions Detail of locking ring Locking ring ...
Page 38: ...INSTALLATION AND WIRING 3 8 ...
Page 48: ...BASIC OPERATIONS 4 10 ...
Page 78: ...LOGIC 5 30 ...
Page 90: ...LOGIC 5 42 ...
Page 102: ...LOGIC 5 54 ...
Page 116: ...LOGIC 5 68 ...
Page 154: ...LOGIC 5 106 ...
Page 231: ...LOGIC 5 183 Chapter 5 ...
Page 307: ...LOGIC 5 259 Chapter 5 ...
Page 319: ...LOGIC 5 271 Chapter 5 ...
Page 331: ...LOGIC 5 283 Chapter 5 ...
Page 386: ...LOGIC 5 338 ...