![IDEC FS1A-C11S User Manual Download Page 178](http://html.mh-extra.com/html/idec/fs1a-c11s/fs1a-c11s_user-manual_617376178.webp)
LOGIC
5-130
Timing chart (Logic 12d)
Example: Manual start input (X12) is used.
Min. 0.1s
Safety output 2:
Y2, Y3
Monitor output for
Safety output 2: Y13
Safety output 1:
Y0, Y1
Monitor output for
Safety output 1: Y12
Safety input 2: X2
Start input 1: X12
(Manual)
Monitor output for
safety input 2: Y5
State monitor output 3:
Y16
Logic function monitor
output 2: Y20
Safety input 2: X3
Max. 6s
Initialization
note 1)
note 1)
Logic function monitor
output 1: Y17
Control input 1: X16
Control input 2: X17
Power
ON
Safety
output
1
ON
Safety
output
2
ON
Max. 0.1s
OFF delay time
OFF delay time
Safety
output
1
ON
Safety
output
2
ON
Safety
output
1
ON
Safety
output
2
ON
(Safety input 1, 3, 4 and 5 are all ON in this chart.)
Note 1) Input monitor error detection time is infinity.
About safety inputs that are not described in this chart, input monitor error detection time is as follows.
The time of dual channel direct opening input (X0, X1) is 0,5s.
The time of dual channel dependent input (X4 to X7) is infinity.
The time of dual channel safety input (X10, X11) is 0,1s.
Refer to the following “Logic functions” for more details.
Summary of Contents for FS1A-C11S
Page 1: ...FS9Z B1218 FS1A C11S Safety Controller SafetyOne User s manual ...
Page 2: ......
Page 10: ......
Page 16: ...PRODUCT SPECIFICATIONS 2 4 Dimensions Detail of locking ring Locking ring ...
Page 38: ...INSTALLATION AND WIRING 3 8 ...
Page 48: ...BASIC OPERATIONS 4 10 ...
Page 78: ...LOGIC 5 30 ...
Page 90: ...LOGIC 5 42 ...
Page 102: ...LOGIC 5 54 ...
Page 116: ...LOGIC 5 68 ...
Page 154: ...LOGIC 5 106 ...
Page 231: ...LOGIC 5 183 Chapter 5 ...
Page 307: ...LOGIC 5 259 Chapter 5 ...
Page 319: ...LOGIC 5 271 Chapter 5 ...
Page 331: ...LOGIC 5 283 Chapter 5 ...
Page 386: ...LOGIC 5 338 ...