LOGIC
5-63
C
h
a
p
te
r 5
●Muting lamp outputs: Y17 and Y20
Muting lamp outputs are used to control muting lamps.
Intended outputs
(Terminal names)
Target safety inputs
(Terminal names)
Description of operation
Muting lamp output 1
(Y17)
Safety input 1
(X0, X1)
The output is ON, during safety input 1 is muting state by
muting input 1.
Muting lamp output 2
(Y20)
Safety input 2
(X4, X5)
The output is ON, during safety input 2 is muting state by
muting input 2.
Warning
The muting lamp outputs are not safety outputs. Do not use these to construct a safety system.
Note. Muting lamp output terminals (Y17 and Y20) detect that muting lamps are disconnected or
unconnected. If these f
ailures are detected, the error LED displays “5” and the state changes to
the Stop state.
Note.
If there is an unused muting lamp output, connect a resistor (10 kΩ, 1/4W) to the unused
terminals.
Caution
Refer to "Chapter 2 PRODUCT SPECIFICATIONS" for specifications of each input and output.
Summary of Contents for FS1A-C11S
Page 1: ...FS9Z B1218 FS1A C11S Safety Controller SafetyOne User s manual ...
Page 2: ......
Page 10: ......
Page 16: ...PRODUCT SPECIFICATIONS 2 4 Dimensions Detail of locking ring Locking ring ...
Page 38: ...INSTALLATION AND WIRING 3 8 ...
Page 48: ...BASIC OPERATIONS 4 10 ...
Page 78: ...LOGIC 5 30 ...
Page 90: ...LOGIC 5 42 ...
Page 102: ...LOGIC 5 54 ...
Page 116: ...LOGIC 5 68 ...
Page 154: ...LOGIC 5 106 ...
Page 231: ...LOGIC 5 183 Chapter 5 ...
Page 307: ...LOGIC 5 259 Chapter 5 ...
Page 319: ...LOGIC 5 271 Chapter 5 ...
Page 331: ...LOGIC 5 283 Chapter 5 ...
Page 386: ...LOGIC 5 338 ...