![IDEC FS1A-C11S User Manual Download Page 21](http://html.mh-extra.com/html/idec/fs1a-c11s/fs1a-c11s_user-manual_617376021.webp)
PRODUCT SPECIFICATIONS
2-9
C
h
a
p
te
r 2
Start input specifications
Rated input voltage
24V DC
Input ON voltage
15.0V DC to 28.8V DC
Input OFF voltage
Open or 0V DC to 5.0V DC
Number of start input terminals
2 (X16,17)
Input current
5mA per port (at rated voltage)
Type of input
Sink type input (for PNP output), Type 1 (EN61131-2)
Cable length
Note1
100m maximum (total wiring length per 1 input)
Allowable wiring resistance
300Ω maximum
Note1. For cables longer than 30m between SafetyOne and connected devices, use grounded
shielded cables to assure electromagnetic compatibility.
Start input equivalent circuit
Start input operating range
The specifications of the start inputs changes depending on the Logic selected. See further
information in “Chapter 5 LOGIC”. But basic specifications are same.
Warning
Do not use start inputs as safety inputs. This may cause the loss of safety functions and
possible failure in the SafetyOne or peripherals.
Voltage(V)
Current
(mA)
28.8
24
15
5
0.5
3
5
6
ON area
Transition area
OFF area
I
n
t
e
r
n
a
l
C
ir
c
u
it
4.7
kΩ
V-
X16, X17
Summary of Contents for FS1A-C11S
Page 1: ...FS9Z B1218 FS1A C11S Safety Controller SafetyOne User s manual ...
Page 2: ......
Page 10: ......
Page 16: ...PRODUCT SPECIFICATIONS 2 4 Dimensions Detail of locking ring Locking ring ...
Page 38: ...INSTALLATION AND WIRING 3 8 ...
Page 48: ...BASIC OPERATIONS 4 10 ...
Page 78: ...LOGIC 5 30 ...
Page 90: ...LOGIC 5 42 ...
Page 102: ...LOGIC 5 54 ...
Page 116: ...LOGIC 5 68 ...
Page 154: ...LOGIC 5 106 ...
Page 231: ...LOGIC 5 183 Chapter 5 ...
Page 307: ...LOGIC 5 259 Chapter 5 ...
Page 319: ...LOGIC 5 271 Chapter 5 ...
Page 331: ...LOGIC 5 283 Chapter 5 ...
Page 386: ...LOGIC 5 338 ...