UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
A Alarm List
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
197
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name
Severity
Cause
Solution
meet
requirements.
0036-2
Battery
maintenance
reminder
Warning
The time for
maintenance arrives.
Maintain the batteries.
0037-1
Battery
undervoltage
Critical
The UPS has
worked in battery
mode for an
extended amount
of time.
The charger is
faulty.
1.
Check whether the battery
voltage is normal.
2.
Check whether the output is
overloaded.
3.
Check whether any battery is
damaged. If yes, replace the
battery.
4.
Check whether any battery
charger generates an alarm. If
yes, replace the faulty module.
0040-7
Rectifier abnormal
Critical
The fan for the
power module is
not functioning
properly.
The air channel
for the power
module is
obstructed.
1.
Check that the air channel for
the module is free from
blockage.
2.
Check whether the fans are
functioning properly. Replace
the power module if the fans
are faulty.
0043-1
Fan abnormal
Critical
The fan for the
power module is
abnormal.
The fan
monitoring cable
for the power
module is not
working
properly.
Replace the faulty power module.
0043-2
The fan is faulty.
Check the fan or replace the
bypass module.
0043-3
The fan is faulty.
The fan
monitoring cable
is faulty.
1.
Replace the fan.
2.
Check the fan monitoring
cable.
0043-4
0047-1
Not ready
Critical
The ready switch is
OFF.
Close the ready switch.
0060-4
Inverter abnormal
Critical
A load
short-circuit
occurs.
1.
Check load cable distributions.
2.
If load cable distributions are
normal, replace the power