UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
A Alarm List
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
201
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name
Severity
Cause
Solution
is OFF.
output breaker open
alarm
has disappeared. If the alarm
persists, tap the
Clear Fault
button to clear the alarm.
0341
PDC Maint. breaker
closed
Minor
The maintenance
circuit breaker on
the PDC is ON.
The running status is displayed.
No further measures are required.
0342
Mains input breaker
open
Critical
The mains input
circuit breaker is
OFF.
The running status is displayed.
No further measures are required.
0343
BPM input breaker
open
Critical
The bypass input
circuit breaker is
OFF.
The running status is displayed.
No further measures are required.
0340
Maint. breaker
closed
Minor
The maintenance
circuit breaker is
ON.
The running status is displayed.
No further measures are required.
0335
Generator
connected
Warning
The generator is
connected.
The running status is displayed.
No further measures are required.
0594-1
Insufficient
redundant racks
Minor
The load is
excessive.
The configured
number of
redundant racks
is incorrect.
1.
Reduce the load.
2.
Decrease the configured
number of redundant racks.
0095-1
Insuffi. redundancy
Minor
The load is
excessive.
The configured
number of
redundant
modules is
incorrect.
1.
Reduce the load.
2.
Decrease the configured
number of redundant modules.
0096-1
ECO volt.
Abnormal
Minor
The ECO bypass
voltage or
frequency is out
of the preset
range.
The ECO bypass
voltage or
frequency range
is incorrectly set.
The bypass input
sequence is
reverse or the
1.
Check the bypass input voltage
and frequency.
2.
Check that the rated voltage,
rated frequency, ECO bypass
voltage range, and frequency
range are correctly set.
3.
Check that the bypass cables
and circuit breakers are
correctly connected.