UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
2 Overview
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
30
Specifications
Hot-swappable
1 U high
2.3.5.3 Dry contact card
Appearance
Figure 2-15
Dry contact card
Table 2-6
Ports on the dry contact card
Silk Screen
Description
Status
Initial Status
BTG
Port for detecting battery
grounding faults
Connected: battery
grounding fault
Disconnected: no
battery grounding
fault
Disconnected
0V
Port for signal ground
GEN
Port for detecting diesel
generator (D.G.) mode
Connected: D.G.
mode
Disconnected:
non-D.G. mode
Disconnected
0V
Port for signal ground
BCB_OL
Port for detecting the BCB
box
Grounded: BCB
box connected
Disconnected:
BCB box not
connected
Grounded
BCB_STA
Port for monitoring the
battery switch
Connected: battery
switch ON
Disconnected:
battery switch
OFF
Disconnected
BCB_DRV
Controls battery circuit
breaker trip. When the
voltage is +12 V, the circuit
breaker trips.
0 V: battery switch
not tripped
12 V: battery
switch tripped
0 V
BCB_0V
Port for signal ground
EPO_NO
Emergency power-off (EPO)
port
If the normally open
(NO) port is
Disconnected