UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
2 Overview
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
25
Indicator
Color
Status
Description
Off
The rectifier CPLD software is being
upgraded.
Alarm
indicator
Yellow
Steady on
A minor alarm is generated for the inverter or
rectifier.
Off
There is no minor alarm for the inverter or
rectifier, or the rectifier CPLD software is
being upgraded.
Fault
indicator
Red
Steady on
A critical alarm is generated for the inverter or
rectifier.
Off
There is no critical alarm for the inverter or
rectifier, or the rectifier CPLD software is
being upgraded.
Functions
The power module consists of a power factor correction (PFC) rectifier, inverter, and DC/DC
converter. The power module performs AC/DC or DC/DC conversion on the mains and
battery inputs, and stabilizes the bus voltage. The inverter (DC/AC) converts the inputs into
sine wave outputs.
Specifications
Dimensions (H x W x D): 130 mm x 442 mm x 620 mm
Weight: ≤ 35 kg
Rated output capacity: 50 kVA/50 kW
Power density: 50 kVA/3 U