Figure 3-10
Dimensions of antiseismic kit mounting holes (unit: mm)
Step 2
Drill holes for installing expansion bolts, and install expansion sleeve.
Step 3
Open the front door of the cabinet and remove the support baffle plates from the front of the
cabinet. Remove the rear cover.
Figure 3-11
Removing support baffle plates
Step 4
Secure the antiseismic kits to the front and back of the cabinet using M6 screws.
Figure 3-12
Securing the antiseismic kits to the cabinet