UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
3 Installation
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
48
Item
350 kVA 400
kVA
450
kVA
500 kVA 550 kVA 600 kVA
PE
Bypass
input
connector
Bypass input current
(A)
532
608
684
760
836
912
Recommended
cross-sectional
area (mm
2
)
L1
2 x (3 x
185 + 1 x
95)
2 x (3 x
240 + 1 x
120)
3 x (3 x
185 + 1
x 95)
3 x (3 x
185 + 1 x
95)
3 x (3 x
240 + 1 x
120)
4 x (3 x
185 + 1 x
95)
L2
L3
PE
Output
connector
Output current (A)
532
608
684
760
836
912
Recommended
cross-sectional
area (mm
2
)
U
2 x (3 x
185 + 1 x
95)
2 x (3 x
240 + 1 x
120)
3 x (3 x
185 + 1
x 95)
3 x (3 x
185 + 1 x
95)
3 x (3 x
240 + 1 x
120)
4 x (3 x
185 + 1 x
95)
V
W
PE
Battery
input
connector
Nominal battery
discharge current (A)
768
877
987
1096
1206
1316
Maximum battery
discharge current (A)
919
1051
1182
1313
1444
1576
Recommended
cross-sectional
area (mm
2
)
+
2 x (2 x
185)
3 x (2 x
185)
3 x (2 x
150)
3 x (2 x
150)
3 x (2 x
240)
3 x (2 x
240)
-
PE
185
185
240
240
240
240
When selecting, connecting, and routing power cables, follow local safety regulations
and rules.
If external conditions such as cable layout or ambient temperatures change, perform
verification in accordance with the IEC-60364-5-52 or local regulations.
If the rated voltage is 400 V, multiply the currents by 0.95. If the rated voltage is 415 V,
multiply the currents by 0.92. If the rated voltage is 420 V, multiply the currents by
0.905.
The nominal battery discharge current refers to the current of forty 12 V batteries at 480
V in standard configuration.
The maximum battery discharge current refers to the current when forty 12 V batteries in
standard configuration, that is, two hundred and forty 2 V battery cells (1.67 V/cell), stop
discharging.
The battery cable specifications are selected based on 40 batteries by default and
compatible with application scenarios with 30–50 batteries.
When the mains input and bypass input share a power source, configure mains input
power cables as input power cables. In addition, cables listed in
apply only to the following conditions: