UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
3 Installation
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
47
Item
50 kVA
100
kVA
150
kVA
200 kVA 250
kVA
300 kVA
input
connector
(A)
Recommended
cross-sectional
area (mm
2
)
L1
3 x 25+1
x 25
3 x 70 +
1 x 35
2 x (3 x
70 + 1 x
35)
2 x (3 x
95 + 1 x
50)
2 x (3 x
120 + 1 x
70)
2 x (3 x
150 + 1 x
70)
L2
L3
PE
Bypass
input
connector
Bypass input current
(A)
76
152
228
304
380
456
Recommended
cross-sectional
area (mm
2
)
L1
3 x 25+1
x 25
3 x 70 +
1 x 35
2 x (3 x
70 + 1 x
35)
2 x (3 x
95 + 1 x
50)
2 x (3 x
120 + 1 x
70)
2 x (3 x
150 + 1 x
70)
L2
L3
PE
Output
connector
Output current (A)
76
152
228
304
380
456
Recommended
cross-sectional
area (mm
2
)
U
3 x 25+1
x 25
3 x 70 +
1 x 35
2 x (3 x
70 + 1 x
35)
2 x (3 x
95 + 1 x
50)
2 x (3 x
120 + 1 x
70)
2 x (3 x
150 + 1 x
70)
V
W
PE
Battery
input
connector
Nominal battery
discharge current (A)
110
219
329
439
548
658
Maximum battery
discharge current (A)
131
263
394
525
657
788
Recommended
cross-sectional
area (mm
2
)
+
2 x 25
2 x 70
2 x 150
2 x (2 x
120)
2 x (2 x
120)
2 x (2 x
150)
-
PE
25
35
70
120
120
150
Table 3-3
Recommended power cable cross-sectional area (350 kVA–600 kVA)
Item
350 kVA 400
kVA
450
kVA
500 kVA 550 kVA 600 kVA
Mains
input
connector
Mains input current (A)
616
704
792
880
968
1055
Recommended
cross-sectional
area (mm
2
)
L1
2 x (3 x
185 + 1 x
95)
2 x (3 x
240 + 1 x
120)
3 x (3 x
185 + 1
x 95)
3 x (3 x
185 + 1 x
95)
3 x (3 x
240 + 1 x
120)
4 x (3 x
185 + 1 x
95)
L2
L3