UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
4 User Interface
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
111
Item
Description
Default
Value
Value
Range
properly connected and that BSC-related
hardware is properly installed.
Figure 4-33
System Settings 2
Item
Description
Default
Value
Value
Range
Altitude
Set this parameter based on the altitude of
the place where the rack is used.
≤ 1000
≤ 1000,
1000–2000,
2000–3000,
3000–4000,
4000–5000
Top outlet fan
Enable this parameter if a top outlet fan is
configured. Then the fan running status can
be checked.
Disable
Disable,
Enable
Air filter
maintenance
period (d)
Specifies the rack air filter maintenance
interval. If it is set to
0
, there is no reminder.
0
0–365
Intra-rack
power module
start delay (s)
These two parameters enable the UPS to
control the interval that each rack (or
module) transfers from battery mode to
normal mode, which reduces the impact on
the generator or power grid. In the case of
battery undervoltage, the system
automatically shortens the delay for
transferring to normal mode to 1/8 of the
normal delay to accelerate the transfer and
prevent battery overdischarge. The start
delay of a module in a rack varies depending
on the rack number and module number. #1
module in rack 1 does not have a start delay.
0.5
0.5–120.0
Inter-rack
power module
start delay (s)
5
2–120