UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
4 User Interface
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
118
Item
Description
Default
Value
Value Range
12 V
battery: 40
30–50
Number of
battery
strings
Specifies the number of battery
strings connected in parallel.
1
1–4
Installation
time
A battery maintenance reminder is
displayed when the maintenance time
(counted from the installation time)
comes.
N/A
N/A
Maintenanc
e period (d)
Specifies the interval for reminding
users of battery maintenance. If this
parameter is set to 0, there is no
reminder.
0
0–365
Chg. cur.
limiting
coef. (C10)
The charging current limit is a
multiple of the battery capacity.
0.10
0.05–0.15
Cell float
voltage
(V/cell)
Specifies the battery float charging
voltage.
2.25
2.23–2.30
Cell
equalized
volt. (V/cell)
Specifies the battery equalized
charging voltage.
2.35
2.30–2.40
Dis. cur.
0.1C EOD
(V/cell)
Specifies the EOD threshold when
the discharging current is 0.1C, 0.3C,
0.5C, and 1.0C respectively.
1.80
1.80–1.90
Dis. cur.
0.3C EOD
(V/cell)
1.80
1.80–1.90
Dis. cur.
0.5C EOD
(V/cell)
1.75
1.75–1.85
Dis. cur.
1.0C EOD
(V/cell)
1.60
1.60–1.75
Sched.
shallow dis.
test
When certain conditions are met, the
charger shuts down, and batteries
supply power to loads. The system
records the battery discharge data as
the reference for battery capacity and
lifespan.
Disable
Disable, Enable
Shallow dis.
test dis.
ratio (%)
Set the proportion of the discharge
capacity to the total discharge
capacity. The value is configurable in
20
10–50