4 User Interface
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
143
Item
Description
Default
Value
Value
Range
disabled, and EOD restart is enabled, the UPS
will restart as soon as the mains resumes. If
EOD restart is disabled, clear the alarm
manually or enable the restart function for the
UPS.
EOD restart
delay (min)
If EOD restart is set to Enable, the UPS starts
working after EOD restart delay when the
mains recovers from an EOD power failure.
10
1–1440
Undertemp.
alarm thresh.
(°C)
Battery temperatures can be monitored in a
timely manner. If a low or high battery
temperature alarm is detected, the charging
current limit decreases to 0.03 CA. Battery
charging stops if a battery overtemperature
protection alarm (when the temperature reaches
the high temperature threshold plus 3°C) is
generated.
–5
–20 to 5
Overtemp.
alarm thresh.
(°C)
50
35–55
Single batt.
float chg.
voltage
deviation alarm
thres. (%)
Single batt. float chg. voltage deviation alarm
thres. (%) and Single batt. dis. voltage deviation
alarm thres. (%) are used to check whether the
cells in each battery string have the same charge
voltage and discharge voltage. When a value
exceeds the specified range, an alarm is
generated. The calculation formula is
(Charge/Discharge voltage – Average
voltage)/Average voltage x 100%.
10
5–30
Single batt. dis.
voltage
deviation alarm
thres.
20
10–30
Batt. charging
capacity
mismatch
After this function is enabled, an alarm is
generated if the configured battery capacity
exceeds the charging capacity of the rack.
Disable
Disable,
Enable
Bat mode shut
In battery mode, the UPS can automatically
power off according to the preset shutdown
delay time. If the parameter is disabled, this
function is not available.
Disable
Disable,
Enable
Backup time
warning
An alarm is generated if this parameter is set to
Enable and the backup time is less than the
warning threshold.
Disable
Disable,
Enable
Remain. cap.
warning
An alarm is generated if this parameter is set to
Enable and the remaining capacity is less than
the warning threshold.
Disable
Disable,
Enable
Intelligent
hibernation
If this parameter is set to Enable, the intelligent
battery hibernation function is enabled.
Disable
Disable,
Enable
Thres. of low
batt. SOC over
dry contact (%)
If an output dry contact is set to Low battery
SOC, and the battery SOC is lower than this
threshold, the output dry contact will output
signals.
70
5–80