UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
A Alarm List
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
202
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name
Severity
Cause
Solution
neutral wire is
disconnected.
0098-1
Bypass current not
shared
Minor
The output and
input circuit
breakers are
OFF.
The length of the
bypass input or
output cables is
incorrect.
The bypass SCR
open-circuits.
1.
Check that the output and
bypass input circuit breakers
on each rack are ON.
2.
Check that bypass input and
output power cables on each
rack meet the length
requirements.
3.
Rectify any bypass SCR
open-circuit.
0150-1
Inverter
asynchronous
Minor
The bypass
frequency
changes fast.
The output
frequency track
rate is incorrectly
set.
1.
Check that the bypass output
frequency does not change
fast.
2.
Check that the
Output freq.
track rate
is properly set.
0101-1
BSC signal
abnormal
Minor
The dual bus
connector is
loose.
Parameters are
set incorrectly.
1.
Check the dual bus connector.
2.
Check the parameter settings.
0102-1
Maint. breaker
misoperation
Critical
The user operation is
incorrect.
1.
Shut down the inverter and
then close the maintenance
circuit breaker.
2.
After maintenance, open the
maintenance circuit breaker
and then start the inverter.
0380
In self-check
Warning
The inverter is in
self-check.
Wait until the inverter self-check
is complete.