5 Operations
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
169
Figure 5-6
Inv. OFF
To shut down the inverter on the
Maintenance
screen, tap
System Info
>
Maintenance
.
On the WebUI
a.
In the browser, enter the UPS IP address in the address box.
b.
On the login page, select a display language, enter a
User name
and
Password
, and
click
Login
.
c.
On the homepage, choose
Monitoring
>
Control
, and click
Inv. OFF
. In the
displayed dialog box, click
OK
to shut down the inverter.
Figure 5-7
Shutting down the inverter
After the inverter shuts down, the UPS works in bypass mode if the bypass is
normal; the UPS supplies no power and the loads power off if the bypass is
abnormal.