UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
8 Technical Specifications
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
192
Item
Specifications
voltage)
Output power factor
1
Transfer time
Uninterruptible transfer: 0 ms
Interruptible transfer: ≤ 20 ms
Output voltage
imbalance
Voltage imbalance: ±3%; phase imbalance: 120±2°
Overload capability
Inverter overload capability:
105% < load ≤ 110%: transfer to bypass mode after 60
minutes
110% < load ≤ 125%: transfer to bypass mode after 10
minutes
125% < load ≤ 150%: transfer to bypass mode after 1 minute
Load > 150% or a short circuit occurs: run for 200 ms
Table 8-8
System electrical specifications
Item
Specifications
Redundancy design
The auxiliary power supplies, centralized controllers, and
parallel signals use redundancy design.
ECO
Supported