A Alarm List
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
199
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name
Severity
Cause
Solution
abnormal
not functioning
properly, or the
air channel is
blocked.
The ambient
temperature
exceeds the
upper threshold.
The load is
excessive.
replace it.
2.
Check that the ambient
temperature has not exceeded
40°C.
3.
Check that there is no
overload.
0583-1
Inter-rack par. cable
abnormal
Critical
The inter-rack
parallel system
CAN bus is
disconnected or
short-circuited.
Only one rack
works in a
parallel system.
An ECM is
faulty.
1.
Check the inter-rack parallel
system CAN bus.
2.
Rectify the disconnection or
short-circuit fault.
3.
Replace the ECM.
0583-4
The inter-rack
industrial frequency
synchronization
cable is broken.
Replace the inter-rack parallel
cable.
0583-5
The inter-rack
carrier
synchronization
cable is broken.
0583-6
The intra-rack
INVBYP cable is
broken.
The parallel
CAN bus is
broken.
0584-2
Inter-rack par. cable
alarm
Minor
The inter-rack
parallel cable is
faulty.
Replace the inter-rack parallel
cable.
0584-4
The inter-rack
industrial frequency
synchronization
cable is broken.
0085-1
EPO
Critical
The EPO button is
pressed.
Restore the EPO button status.
Start the UPS after the alarm is