UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
8 Technical Specifications
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
190
Item
Specifications
IEC62040-1: 2013
CQC3108-2011
YD/T1095-2000
GB/T4715-93
EMC
FCC Part15 Class A (480 V)
EN62040-2
EN61000-4-3
EN61000-4-6
IEC62040-2
IEC61000-2-2
IEC61000-4-2
IEC61000-4-3
IEC61000-4-4
IEC61000-4-6
IEC61000-4-8
IEC61000-4-11
Table 8-4
Mains input electrical specifications
Item
Specifications
Input system
Three-phase, three-wire, and PE; does not support Δ-type
transformer input; supports only Y-type transformer input
Rated input voltage
380 V AC/400 V AC/415 V AC/420 V AC/480 V AC (line
voltage)
Input voltage
380 V AC/400 V AC/415 V AC/420 V AC voltage system,
0–40°C environment: not derated at 304–485 V AC, derated
at 138–304 V AC
480 V AC voltage system, 0–40°C environment: not derated
at 384–528 V AC, derated at 192–384 V AC
Rated frequency
50 Hz or 60 Hz
Input frequency
40–70 Hz
Input PF
> 0.99 (full load)
> 0.98 (half load)
THDi
THDi ≤ 3% (full linear load)
THDi ≤ 5% (full non-linear load)