4 User Interface
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
107
Figure 4-27
ModbusTCP Settings
Item
Description
Default
Value
Value
Range
ModbusTCP
encryption
If Modbus TCP is used for communication,
communication links do not implement
encryption or implement encryption based on
the selected encryption mode.
Enable
Disable,
Enable
On the
Comm Settings
screen, tap
Amb T/H Sensor
. The
Amb T/H Sensor
screen is
displayed.
Figure 4-28
Amb T/H Sensor
Item
Description
Default
Value
Value
Range
Start
address
–
32
32–44
Quantity
Number of cascaded ambient temperature and
humidity sensors.
0
0–4