4 User Interface
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
138
4.2.2.2 Real-time Data Page
The
Real-time Data
page details real-time system running data.
Figure 4-72
Real-time Data
4.2.2.3 Param. Settings Page
Set system parameters, input parameters, output parameters, bypass parameters, battery
parameters, and dry contacts on the
Param. Settings
page.
Figure 4-73
Param. Settings
Table 4-6
System Setting
Item
Description
Default
Value
Value
Range
High ambient
temperature
alarm threshold
(°C)
An alarm is generated when the ambient
temperature reaches or exceeds the threshold
specified by this parameter.
55
40–60
Low ambient
temperature
alarm threshold
(°C)
An alarm is generated when the ambient
temperature is lower than the threshold
specified by this parameter.
–10
–20 to 0
EPO detection
Indicates whether to enable emergency
power-off (EPO). EPO is performed only when
this parameter is enabled and the EPO switch is
triggered. When EPO detection is changed
from Disable to Enable, check that the EPO
cable is connected correctly.
Disable
Disable,
Enable