PowerWalker VFI 1000 R1U 

Quick Guide 

 

I.

 

Front View 

 

 

Turn on the UPS: Press and hold button for at least 2 seconds to turn on the 
UPS. 

 

Turn off the UPS: Press and hold this button at least 2 seconds to turn off 
the  UPS.  UPS  will  be  in  standby  mode  when  utility  power  is  normal  or 
transfer to bypass mode if bypass mode is enabled via software.

 

 

UPS Status 

LED 

Color 

Mode 

Line Mode 

LED1 

Green 

Lighting 

LED4 to LED7 indicate load level during 

line mode. 

LED4: > 75% load level LED5: 50% ~ 

75% load level 

LED6: 25% ~ 50% load level 

LED7: 0% ~25% load level 

Green 

Lighting 

Battery Mode 

LED2 

Yellow 

Flashing 

LED4 to LED7 indicate battery 

Power during battery mode. 

LED4: battery voltage > 26V 

LED5: battery voltage > 24.5V 

LED6: battery voltage > 23V 
LED7: battery voltage > 21V 

Green 

Lighting 

Summary of Contents for VFI 1000 R1U

Page 1: ... or transfer to bypass mode if bypass mode is enabled via software UPS Status LED Color Mode Line Mode LED1 Green Lighting LED4 to LED7 indicate load level during line mode LED4 75 load level LED5 50 75 load level LED6 25 50 load level LED7 0 25 load level Green Lighting Battery Mode LED2 Yellow Flashing LED4 to LED7 indicate battery Power during battery mode LED4 battery voltage 26V LED5 battery ...

Page 2: ...rnal battery connector III The pin assignment for dry contact Condition Pin status Yes No Low battery Pin 3 and Pin 9 are connected Pin 3 and Pin 1 are connected Output is abnormal Pin 7 and Pin 8 are connected Pin 7 and Pin 5 are connected Battery mode Pin 2 and Pin 6 are connected Pin 2 and Pin 4 are connected IV Disable Enable ROO RPO function Contact open UPS shuts down Contact closed UPS star...

Page 3: ...on de activate external remote contact Fault LED 3 will be OFF and restart the UPS by pressing button V Audible Alarm Battery Mode Sounding every 4 seconds Low Battery Sounding every second Overload Sounding twice every second Fault Continuously sounding Bypass Mode Sounding every 10 seconds ...

Page 4: ...ut voltage 220 230 240 VAC 1 Frequency Range 57 63 Hz Synchronized Range Frequency Range Bat Mode 60Hz 0 3 Hz Overload 100 105 audible warning 105 130 10s Current Crest Ratio 3 1 Harmonic Distortion 3 Linear Load 5 Non linear Load Transfer Time to Bat Mode Zero Inverter to Bypass 4 ms Typical Waveform Bat Mode Pure Sinewave EFFICIENCY AC Mode 86 100 load Battery Mode 83 100 load BATTERY Battery 4x...