Summary of Contents for GXT2-6000 RT208

Page 1: ...POWER AVAILABILITY GXT2 6000RT208 USER MANUAL 120 208V 120 240V ...

Page 2: ......

Page 3: ...on Box 8 5 0 WHAT S INCLUDED 9 6 0 INSTALLATION AND CONFIGURATION 10 6 1 Install the Main Cabinet 10 6 1 1 Tower UPS Installation 10 6 1 2 Installing the Adjustable Rack Mount Kit Sold Separately 11 6 2 External Battery Cabinet Installation 13 6 3 Connect Input Output Power 14 6 3 1 Replacing a power distribution box 14 6 3 2 Distribution Box Electrical Connections 14 6 3 3 PD HDWR and PD HDWR MBS...

Page 4: ... N Reverse Detection 120V UPS Models Only 23 8 5 4 Frequency Selection 24 8 6 Options Tab 24 8 7 Options Tab Used With Earlier GXT 2U Models 25 8 8 Battery Tab 26 8 8 1 Low Battery Time Warning 26 8 8 2 Auto Battery Test Time 26 8 8 3 Battery Cabinets Number 26 8 8 4 Auto Battery Test 26 8 9 About Tab 27 9 0 CONTROLS AND INDICATORS 28 9 1 ON Alarm Silence Battery Test Button 28 9 2 OFF Bypass Butt...

Page 5: ...31 11 1 2 Communications SNMP Web Card SNMP Adapter 31 11 2 Pin 4 Remote Shutdown on Battery 32 11 3 UPS Intelligent Communications 32 11 4 Remote Emergency Power Off 33 12 0 MAINTENANCE 34 12 1 Battery Replacement 34 12 1 1 Internal Battery Replacement Procedures 34 12 2 UPS Replacement 35 13 0 TROUBLESHOOTING 36 13 1 Auto Learning Battery Run Times 40 14 0 SPECIFICATIONS 41 14 1 Product Warranty...

Page 6: ... connections 33 TABLES Table 1 Electrical requirements PD HDWR and PD HDWR MBS 15 Table 2 Electrical requirements PD 001 15 Table 3 DB 9 pin assignment 31 Table 4 Fault indicators 36 Table 5 Alarm conditions 37 Table 6 Troubleshooting guide 37 Table 7 Battery run times 39 Table 8 UPS specifications 41 Table 9 Battery specifications 42 Table 10 Power distribution box specifications 42 Table 11 Exte...

Page 7: ...ants moisture flam mable liquids gases and corrosive substances This UPS contains no user serviceable parts except the internal battery pack The Off Bypass push button does not electrically isolate internal parts Under no circumstances attempt to gain access internally other than to replace the batteries due to risk of electric shock or burn Do not continue to use the UPS if the front panel indica...

Page 8: ... is harmful to skin and eyes It may be toxic CAUTION A battery can present a risk of electrical shock and high short circuit current The following precautions should be observed when working on batteries Remove watches rings and other metal objects Use tools with insulated handles Wear rubber gloves and boots Do not lay tools or metal parts on top of batteries Disconnect charging source prior to c...

Page 9: ...n followed by important instructions AC input AC output Requests the user to consult the manual Indicates the unit contains a valve regulated lead acid battery Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage ON Alarm Silence Battery Test OFF Bypass i PbH2SO4 R ...

Page 10: ...ts output voltage whether utility power is present or not It supplies connected equip ment with clean sinewave power Sensitive electronic equipment operates best from sinewave power For ease of use the UPStation GXT2 6000RT208 features a light emitting diode LED display to indicate both load percentage and battery capacity It also provides self diagnostic tests a combina tion ON Alarm Silence Batt...

Page 11: ...distortion reflected on the utility is reduced This results in cleaner power being available to other devices in the building not being protected by the UPStation GXT2 6000RT208 3 3 Inverter In normal operation the inverter utilizes the DC output of the power factor correction circuit and inverts it into precise regulated sinewave AC power Upon a utility power failure the inverter receives energy ...

Page 12: ...al battery cabinets are available to extend battery run times 3 7 Dynamic Bypass The UPStation GXT2 6000RT208 provides an alternate path for utility power to the connected load in the unlikely event of a UPS malfunction Should the UPS have an overload overtemperature or UPS failure condition the UPS automatically transfers the connected load to bypass Bypass operation is indicated by an audible al...

Page 13: ...ulled forward and removed to reveal the battery access door The internal battery pack is a compact assembly ready to slide into the battery compartment after the front battery access door has been opened Electrical connection is automatic upon insertion UPStation GXT Input Circuit Breaker Support Base Hardwire Knockouts External Battery Connector Cooling Fan 1 of 4 Intellislot Port REAR VIEW FRONT...

Page 14: ...vide the ben efits of hardwire input and output plus manual bypass switch or plug receptacle convenience with manual bypass switch DISCONNECT BYPASS POWER TO THE MANUAL BYPASS SWITCH PD HDWR Power Distribution Box With Hardwire Connections Standard Ships With UPS PD HDWR MBS Power Distribution Box With Hardwire Connections and Manual Bypass Switch Optional PD 001 Power Distribution Box With Wired ...

Page 15: ...figuration program disk Ferrite beads 2 UPStation GXT L1 L2 AC INPUT BATTERY UPS ON BYPASS MultiLink software CD Mounting hardware Front bezels Vertical display overlay Rack mount handles MultiLink serial cable 10 ft 3m Top bezels tower use Configuration disk www liebert com GXT 2U Configuration Program For use with LiebertGXT2U model UPS systems Version 1 6 For Windows 95 98 NT To Install Choose ...

Page 16: ...it or in a rack depending on available space and use considerations Determine the type of installation and follow the appropriate instruc tions in either 6 1 1 Tower UPS Installation or 6 1 2 Installing the Adjustable Rack Mount Kit Sold Separately 6 1 1 Tower UPS Installation When using the GXT2 6000RT208 in a tower configuration use the included support base shown below left to stabilize the UPS...

Page 17: ... 2 Determine the height position inside the rack enclosure where you want to mount the UPS or battery cabinet 3 Install the rear member of each bracket assembly into rack enclosure with two 2 M5 screws provided in this kit see figure at right The return flanges on the bracket assembly fit to the inside of rack mounting rails Insert screws loosely finger tight into the top and bottom holes of the r...

Page 18: ...mbers attached in Step 5 into the bracket assemblies by inserting the top and bottom edges of the inner members into the top and bottom curved tracks of the front members and sliding the equipment into the rack see figure at right Ends of inner members are tapered to allow the rear of the equipment to be angled upward before insertion if space allows Then the rear bottom edges of the inner members...

Page 19: ...One additional set of support base extensions ships with each external battery cabinet 4 Connect the supplied external battery cabinet cable to either of the connectors on the rear of the external battery cabinet then to the rear of the UPS 5 The UPS is now equipped with additional backup battery run time For approximate battery run times refer to Table 7 Battery run times in this manual 6 Do NOT ...

Page 20: ...olding the box firmly against the UPS tighten the three captive mounting screws until the box is secure Do not overtighten 6 3 2 Distribution Box Electrical Connections Electrical connections are made through a removable power distribution box that attaches to the rear of the UPS The installer must provide a 30A branch circuit breaker The input circuit breaker on the distribution box and the outpu...

Page 21: ...nded Wire including ground wire 75 C copper wire Maximum Wire Accepted by Terminal Block Terminal Tightening Torque 24A 30A 10 AWG 8 AWG 20 in lb NOTE 1 The installer must provide circuit breaker protection according to local codes The utility disconnect should be within sight of the UPS or have an appropriate lock out Maintain service space around the UPS or use flexible conduit 2 The installer m...

Page 22: ...t the internal battery installed Once the UPS is installed in place the internal battery pack must be installed 1 Unpack the internal battery from its shipping container 2 Lift the battery pack from its container holding it in the center of the pack Do NOT lift the battery pack by grasping the connector on the rear 3 Align the battery pack so that the rear connector is nearest the control panel 4 ...

Page 23: ...tch is used the Bypass lamp will light by the switch If no manual bypass switch is used there will be no output voltage at this time b If the configuration program has been used to set the L N voltage at 100 110 or 115 then the input phase angle is required to be 180 degrees c If the configuration program as been used to set the L N voltage at 127 VAC then the input phase angle is required to be 1...

Page 24: ... the input circuit breaker located on the distribution box The green Line lamp should illuminate on the front panel 10 Press the Start button for 1 second The Bypass lamp will light for several seconds before the Inverter lamp turn on continuously If the batteries are determined to charged above 80 an automatic battery test will run for about 15 seconds 11 Close the output circuit breaker on the r...

Page 25: ...110 115 or 120 VAC The nominal L1 L2 voltages for these four settings will be 200 220 230 or 240 VAC respec tively If the measured L1 L2 voltage is equal to the average L N voltage times 1 73 then the phase angle is 120 degrees and the L N VAC may be set at either 120 or 127 VAC The nominal L1 L2 voltages for these two settings will be 208 or 220 VAC respectively Selecting a L N nominal voltage th...

Page 26: ... updated version 1 Use the Windows Explorer to find and open the Lbt_gxt2 1 6 exe installation program on the included software CD 2 When you see this PreSetup window select OK This will open the main installation screen 3 Click NEXT to continue installing the configuration program Liebert recommends using the default installation options but you will be given the option to make modifications to t...

Page 27: ...T 2U UPS When the UPS is found the opening program window will display the UPS model If the configuration program ever fails in its attempt to read data from a UPS the error message below will be displayed The program must communicate with the UPS when it first opens when a new tab is opened and when the REFRESH APPLY or OK buttons are pressed If this message is displayed check the following items...

Page 28: ...he UPS OFF Bypass button twice within four seconds hold the button one second each time This will disconnect all power to the load Changing any value or selecting deselecting any setting in the configuration window will not immedi ately change the settings in the UPS You may modify the displayed settings until you are satisfied with the new proposed changes Settings displayed by the configuration ...

Page 29: ...g system to limit battery depletion serial data or contact closure If Auto Restart is enabled check mark in box the UPS will restart when input power is restored If the UPS turns off power to the load for any other reason manual restart is required See 8 6 Options Tab for exceptions Click on the box to remove the check mark and disable Auto Restart 8 5 3 L N Reverse Detection 120V UPS Models Only ...

Page 30: ...elay contact signals The Options tab expands the UPS versatility for such applications Refer to your UPS manual for a description of the 9 pin communication connector on the rear of the UPS Pin 6 of the 9 pin communication connector is used for Any Mode Shutdown of the UPS out put This control input may be used in special applications to disable the UPS output power both Inverter and Bypass The Op...

Page 31: ...s tab If version 1 6 or later is used with an earlier GXT 2U model with an earlier UPS firmware version the Any Mode Shutdown features cannot be changed If the configuration program is used with an earlier UPS model with an earlier UPS firmware ver sion that does not support the modification of these settings the Options tab will display a reminder of the factory default settings as shown These ca...

Page 32: ...rforms an automated battery test periodically if enabled The user may also select time periods of 7 14 21 and 28 days 8 8 3 Battery Cabinets Number If additional batteries are attached to the UPS accurate battery runtime estimates are possible if the battery number and type of batteries are entered here The new UPS models are designed to operate with up to four external battery packs or four long ...

Page 33: ...Configuration Program 27 8 9 About Tab The version number of the configuration program may be confirmed using the About Tab ...

Page 34: ... After the batteries have been retested if only three of the five Battery indicators illuminate con tact your local dealer Liebert representative or Liebert Worldwide Support Group 9 2 OFF Bypass Button This button controls output power to connected load s and has dual functions OFF and Bypass Pressing the OFF Bypass button twice within 4 seconds shuts off power to the output receptacles and conne...

Page 35: ...d Fault indicator along with the A and C diagnostic indicators will illuminate and an alarm will sound refer to 13 0 Troubleshooting The remote test feature functions with MultiLink 3 software and can remotely initiate the battery test 9 5 Fault Indicator Red The Fault indicator is illuminated if the UPS has detected a problem Also one or more of the Battery Level indicators may be illuminated ref...

Page 36: ...ds every 10 seconds This will change to two beeps every 5 seconds when the battery runs low approximately 2 minutes remaining but this is user configurable The AC Input indicator will extinguish and the Battery indicator will illuminate to warn that a utility problem has occurred Each Battery Level indicator repre sents a 20 capacity level As capacity decreases fewer indicators remain illuminated ...

Page 37: ...d clamp to the network cable see illustration at right using the following directions 1 Open the ferrite bead 2 Place the network cable inside the ferrite bead groove 3 Wrap the cable once around the ferrite bead 4 Position the ferrite cable as close as possible to the end of the cable that connects to the UPS 5 Close the ferrite bead so that the ferrite bead s case snaps closed with the cable rou...

Page 38: ...after performing the 2 minute shutdown delay 11 3 UPS Intelligent Communications The UPStation GXT2 6000RT208 is equipped with an Intellislot port to provide advanced communi cation and monitoring options Liebert s MultiLink software continually monitors the UPS and can shut down your computer or server in the event of an extended power failure MultiLink can also be configured for use without the ...

Page 39: ...ected equipment to comply with national and local wiring codes and regulations Figure 5 REPO switch connections CAUTION To maintain safety SELV barriers and electromagnetic compatibility signal cables should be segregated and run separately from power cables REPO connections for normally open switch system REPO as shipped REPO connections for normally closed switch system fail safe 1 2 3 4 Key to ...

Page 40: ...d to support the weight of the battery as it is withdrawn 4 Unpack the new battery assembly taking care not to destroy the packing Compare new and old battery assemblies to make sure they are the same If so proceed with Step 6 otherwise STOP and contact your local dealer Liebert representative or the Liebert Worldwide Support Group 5 Line up and slide in the new replacement battery pack 6 Reattach...

Page 41: ... cover in place 7 Replace the UPS 8 Loosen the three screws holding the electrical connector cover again one turn each 9 Slide the cover away from the electrical connectors gently retighten the three screws 10 Align the connectors on the power distribution box and the UPS 11 Push the power distribution box into place 12 Holding the power distribution box firmly against the UPS tighten the three ca...

Page 42: ... C On bypass due to control power supply failure on L1 1 second beep every 4 seconds On bypass due to control power supply failure on L2 2 second beep every 4 seconds Indicator D On bypass due to PFC failure on L1 1 second beep every 4 seconds On bypass due to PFC failure on L2 2 second beep every 4 seconds Indicator E On bypass due to inverter failure on L1 1 second beep every 4 seconds On bypass...

Page 43: ... in Battery Mode Save data and close applications Replace UPS input fuse then restart UPS Utility voltage out of UPS input range UPS is operating in Battery Mode Save data and close applications Ensure utility supply voltage is within acceptable limits for UPS UPS has reduced battery time Batteries are not fully charged Keep UPS plugged in continuously at least 24 hours to recharge batteries UPS i...

Page 44: ...rrently activated UPS has shut down due to the REPO Remote Emergency Power Off The output cannot be started by any method Fault indicator and diagnostic indicators B and D are illuminated UPS output is OFF from a previous REPO command REPO is no longer activated UPS is OFF due to previous REPO REPO is no longer activated Once utility power is restored press the OFF button twice within four seconds...

Page 45: ...Run Time in Minutes Internal Battery 10 75 20 38 30 25 40 18 50 14 60 11 70 9 80 7 90 6 100 5 Internal Battery 1 External Battery Cabinet 10 156 20 90 30 62 40 44 50 34 60 28 70 23 80 19 90 16 100 14 Internal Battery 2 External Battery Cabinets 10 235 20 137 30 99 40 74 50 58 60 47 70 39 80 33 90 28 100 25 Internal Battery 3 External Battery Cabinets 10 313 20 183 30 133 40 103 50 82 60 67 70 55 8...

Page 46: ...PS will update the anticipated run time calculation only under certain conditions The UPS must have a steady load that is greater than 20 The UPS must be at 100 charge at the start of a battery discharge The battery discharge must continue uninterrupted until the batteries reach their end of dis charge voltage If all conditions are not met the run time calculation will not be modified If the confi...

Page 47: ...ttery Operation Except 100 VAC L N Operation 100 90 loading 90 VAC 140 VAC 90 70 loading 80 VAC 140 VAC 70 30 loading 70 VAC 140 VAC 30 0 loading 60 VAC 140 VAC L1 N L2 N Operating Voltage Range Without Battery Operation 100 VAC L N Operation 100 70 loading 80 VAC 140 VAC 70 30 loading 70 VAC 140 VAC 30 0 loading 60 VAC 140 VAC L1 N L2 N Max Allowable VAC 150 VAC Input Frequency w o Battery Operat...

Page 48: ... Up Time See Table 7 Battery run times Recharge Time 6 Hours to 90 capacity after full discharge into 100 load Table 10 Power distribution box specifications Model Number PD HDWR Amp Rating 24 Amps Input Power Connection 4 Wire Hardwired 8 10AWG Output Power Connection 4 Wire Hardwired 8 10AWG Input Branch Circuit Breaker 30 Amp Supplied by User Model Number PD HDWR MBS Amp Rating 24 Amps Input Po...

Page 49: ...x 618 x 430 Shipping W x D x H 10 5 x 27 2 x 23 268 x 692 x 585 WEIGHT lbs kg Unit 93 6 42 5 Shipping 105 47 6 BATTERY PARAMETERS Type Valve regulated non spillable flame retardant lead acid Qty x V x Rating 12 x 12V x 9 0 AH Battery Mfg Part Yuasa REW 45 12 FR Back Up Time See Table 7 Battery run times ENVIRONMENTAL Operating Temp 32 F to 104 F 0 C to 40 C Storage Temp 5 F to 122 F 15 C to 50 C R...

Page 50: ...Specifications 44 ...

Page 51: ......

Page 52: ...s all liability for damages resulting from use of this information or for any errors or omissions 2003 Liebert Corporation All rights reserved throughout the world Specifications subject to change without notice Liebert and the Liebert logo are registered trademarks of Liebert Corporation All names referred to are trademarks or registered trademarks of their respective owners SL 23170 8 03 Rev 0 T...