UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
3 Installation
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
51
3.1.1.2 Installation Clearances
Figure 3-1
Cabinet dimensions (unit: mm)
Reserve the following clearances around the cabinet to facilitate operations and ventilation:
Reserve a clearance of at least 950 mm from the front of the cabinet for ventilation and
operations.
Reserve a clearance of at least 500 mm from the top of the cabinet for operations.
Reserve a clearance of at least 500 mm from the rear of the cabinet for ventilation.
−
Reserve a clearance of at least 800 mm if you need to perform operations at the rear
of the cabinet.
−
If the top air-flow cabinet is configured, no space is reserved at the rear.
3.1.2 Tools and Instruments
Insulate installation tools to prevent electric shocks.
Prepare the following tools and meters indicated in Table 3-1 for installation.
Table 3-1
Tools and meters
Tools and Meters
Electric pallet truck
Manual pallet truck
Ladder
Rubber mallet