UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
5 Operations
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
151
Procedure
Step 1
Choose
Query > Export Data
>
Export Historical Data
, set
Encryption Password for
Export
, and select
Historical Alarm
from the
Data Type
drop-down list.
Figure 5-16
Exporting historical data
Step 2
Click
Export Historical Data
and save the displayed webpage.
----End
5.10 Setting Hibernation Mode
Prerequisites
Ensure that the load power is stable. If the system load power fluctuation is greater than the
rated capacity of half a module (for example, the single-phase load power fluctuation is
greater than 16.67 kVA for a 100 kVA module), the UPS may enter and exit from hibernation
mode repeatedly.
Context
When the load power is small and stable, you can shut down the inverters in some power
modules so that these power modules enter hibernation mode and other power modules bear
more load power. This improves the system efficiency in the case of small load power and
increases the power module service life. The hibernation function can be set on the WebUI.
Procedure
Step 1
On the WebUI, choose
Monitoring
>
UPS System
>
Running Parameter
, and set
Paral sys
hibernate
to
Enable
.
Step 2
Set
Module cycle hiber period(d)
to an integer ranging from 1 to 100. The default value is
30
.