An alarm is generated.
5.6.2.2 Performing a Capacity Test
Context
Before performing a capacity test, ensure that:
The UPS is working in normal mode; float charging or hibernation has lasted for 2 hours
after the SOC reaches 100%; the load rate fluctuation is less than 10%.
The UPS generates no battery overtemperature, overvoltage, or overcurrent alarm. No
generator is connected to the UPS.
The mains, batteries, charger, and discharger are normal. No overload alarm is generated.
The SmartLi generates no alarms related to lithium batteries.
Procedure
Step 1
On the home screen of the LCD, choose
System Info
>
Maintenance
>
Battery Maint.
Step 2
Tap
Start
on the right of
Capacity Test
to start a capacity test.
Figure 5-13
Starting a capacity test
The capacity test automatically stops in any of the following cases:
The minimum electrochemical cell voltage reaches 2.65 V.
The load fluctuation exceeds 10%.
An alarm is generated.
The test is complete when the minimum cell voltage reaches 2.65 V. The test data is obtained from the
capacity test. Save the test data obtained from the latest 36 tests.
----End