UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
4 User Interface
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
108
Item
Description
Default Value Value Range
dis. test
interval(d)
scheduled shallow discharge test.
Shallow dis.
test dis.
ratio(%)
Specifies the proportion of the
discharge capacity to the total
discharge capacity. The value is
configurable in any mode.
20
10–50
Cell charge
voltage(V/cell)
Specifies the charge voltage of
lithium batteries (the value is
automatically obtained).
N/A
N/A
Chg. cur.
limiting
coef.(C)
Lithium battery: You can set the
charge current limit value. The
current limit coefficient is a
multiple of the battery capacity.
0.50
0.10–1.00
Lead-acid battery: You can set
the charge current limit value.
The current limit coefficient is a
multiple of the battery capacity.
0.10
0.05–0.15
iBOX Settings
Figure 4-28
iBOX Settings
If lead-acid batteries are used and
Number of iBOXs
in
System Info
>
Settings
>
iBOX Settings
>
Basic Param.
is not
0
,
Batt. String Config
is displayed on the
iBOX Settings
screen.