UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
A (Optional) TN-C System Application
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
165
A
(Optional) TN-C System Application
If the TN-C system is adopted, short-circuit the input N and PE, and connect the input PE and
N to terminals on the N bar.
Recommended cable cross-sectional area: 240 mm
2
Recommended screw: M16
Figure A-1
Short-circuiting the input N and PE (side view)