Specifications
Hot-swappable
1 U high
2.5.5.3 Dry Contact Card
Appearance
Figure 2-18
Dry contact card
For dry contact outputs, the rated DC voltage and current are 24 V DC and 0.6 A and the
maximum values are 30 V DC and 1.0 A. The rated AC voltage and current are 24 V AC and
0.6 A and the maximum values are 30 V AC and 1.0 A. During cable connection, ensure that
the voltage and current do not exceed these maximum values.
Table 2-6
Functions of control signal ports on the dry contact card
Silk Screen
Signal Description
Status Description Initial
Status
BTG
Port for monitoring battery
grounding failures
Closed: There is a
battery grounding
Open