4 User Interface
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
102
Item
Description
Default Value Value Range
[B_TEMP]
temperature near batteries. It
ensures that batteries work
reliably and safely.
BCB trips if
UPS stops
power supply
Specifies whether the BCB trips
when the UPS stops supplying
power and the output power is
off.
Enable
Disable, Enable
Intelligent
detection
module
If this parameter is set to
Enable
,
Intelli Temp Detect
is displayed
on the
Runn. Info.
screen.
Enable
Disable, Enable
Switch cabinet
Enable this parameter when a
switch cabinet is installed. After
this parameter is set to
Enable
,
the running status of the switch
cabinet can be detected.
Disable
Disable, Enable
Top outlet
cabinet
Enable this parameter when a top
air-flow cabinet is installed.
Disable
Disable, Enable
Bottom cable
entry cabinet
Enable this parameter when a
bottom cabling cabinet is
installed.
Disable
Disable, Enable
Input Settings
Figure 4-23
Input Settings screen
Item
Description
Default Value Value Range
D.G. mode
Set this parameter to
Enable
when a DG connects to the input
power distribution cabinet
(PDC). The UPS enters the DG
mode when a DG is detected
Disable
Disable, Enable