UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
B Alarm List
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
172
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name Severity
Possible Cause Suggestion
upper
threshold.
The loads are
excessive.
0583-1
Inter-rack par.
cable
abnormal
Critical
The
inter-rack
parallel CAN
bus is
disconnected
or
short-circuits.
Only one
UPS works in
a parallel
system.
An ECM is
faulty.
1.
Check the CAN bus.
2.
Rectify the disconnection or short circuit
fault.
3.
Replace the ECM.
0583-4
The inter-rack
industrial-freque
ncy
synchronization
cable is
disconnected.
Replace the inter-rack parallel cable.
0583-5
The inter-rack
carrier
synchronization
cable is
disconnected.
0583-6
The
intra-rack
INVBYP
cable is
disconnected.
The parallel
CAN bus is
disconnected.
0584-2
Inter-rack par.
cable alarm
Minor
The inter-rack
parallel cable is
faulty.
Replace the inter-rack parallel cable.
0584-4
The inter-rack
industrial-freque
ncy
synchronization
cable is