UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
5 Operations
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
150
5.8 Clearing the EPO State
Procedure
Step 1
Clear the EPO state of the system. Check that the external EPO switch connected to the dry
contact is in non-EPO state or insert the 4-pin terminal on the EPO port of the dry contact
card.
Step 2
Clear the EPO alarm.
On the LCD
Choose
System Info
>
Alarms
and tap
Clear Faults
. After confirmation, the EPO alarm
is cleared.
On the WebUI
Choose
Monitoring
>
UPS System > Running Control
>
System Commands and
Tests
and click
Clear Faults
. The EPO alarm is cleared.
Step 3
View active alarms and check that the EPO alarm is cleared. If the system bypass input is
normal, the UPS transfers to bypass mode.
On the LCD
Choose
System Info
>
Alarms
>
Active Alarms
to check that the EPO alarm has been
cleared.
On the WebUI
Choose
Home
>
Active Alarm
to check that the EPO alarm has been cleared.
Step 4
Start the inverter.
----End
5.9 Exporting Data
Prerequisites
You have logged in to the WebUI.
Context
The following data can be exported:
Historical alarms
Active alarms
Performance data
Operation logs
E-label
Fault information
This procedure describes how to export historical alarms.