UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
2 Overview
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
28
2.5.3 Power Module
Appearance
Figure 2-13
Power module
(1) Handle
(2) Positioning lock
(3) Running indicator
(4) Alarm indicator
(5) Fault indicator
(6) Ready switch
(7) Output ports
(8) Input ports
Table 2-2
Indicator description
Indicator
Color
Status
Description
Running
indicator
Green
Steady
on
The system is working in inverter mode.
Blinking
at long
intervals
The inverter is ready and in standby state (blinking
at 0.5 Hz, on for 1s and off for 1s).
The inverter is not started (blinking at 0.2 Hz, on
for 2.5s and off for 2.5s).
Blinking
at short
intervals
The module is not configured, the inverter software
and rectifier software are being upgraded, or the
inverter software is being upgraded (blinking at 4 Hz,
on for 0.125s and off for 0.125s).