UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
B Alarm List
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
166
B
Alarm List
This table lists only common alarms. For more information, contact Huawei technical support.
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name Severity
Possible Cause Suggestion
0001-1
Mains voltage
abnormal
Minor
Cable
connections
are incorrect.
The mains is
abnormal.
The power
module is
faulty.
The output or
battery is
incorrectly
grounded.
1.
Check whether cables to mains are
disconnected, loose, or incorrectly
connected.
2.
If cable connections are correct, measure
the mains voltage with a multimeter. If
the mains voltage is greater than 280 V,
the mains input is abnormal; if the mains
voltage is less than 272 V, the sampling
circuit of the power module is abnormal.
Replace the faulty power module.
3.
Check whether the output or battery is
incorrectly grounded.
0001-2
Cable
connections
are incorrect.
The mains is
abnormal.
The mains
input fuse for
the power
module is
blown.
1.
Check whether cables to mains are
disconnected, loose, or incorrectly
connected.
2.
If cable connections are correct, measure
the mains voltage with a multimeter. If
the mains voltage is lower than 80 V,
the mains input is abnormal; if the mains
voltage is greater than 88 V, the
sampling circuit or the fuse of the power
module is abnormal. Replace the faulty
power module.
0001-3
The mains is
abnormal.
Check the mains input frequency.
0004-1
Mains ph.
Reversed
Minor
Cable
connections are
incorrect.
Check cable connections.