UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
8 Technical Specifications
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
163
Item
Specifications
Charging voltage (VRLA
battery)
Equalized charging voltage: 2.35 V/cell
Float charging voltage: 2.25 V/cell
Battery type
VRLA
SmartLi
The UPS supports the SmartLi. For details about the parameters, see the
SmartLi User
Manual
.
Table 8-8
Output electrical specifications
Item
Specifications
Power system
Three-phase four-wire + PE
Voltage
380 V AC/400 V AC/415 V AC (line voltage)
Frequency
In normal mode, the frequency is synchronous with the
bypass input frequency.
In battery mode, the frequency is 50 Hz/60 Hz with a
tolerance of ±0.05%.
Voltage distortion
THD < 1% (linear load)
THD < 3% (non-linear load)
Power factor
1
Transfer time (normal)
Uninterruptible transfer: 0 ms
Interruptible transfer: < 5 ms
Output voltage imbalance
Voltage imbalance: ±3%
Phase imbalance: 120±1° (balanced load), 120±2° (unbalanced
load)
Overload capability
Inverter overload capability:
100% < load ≤ 110%: The UPS transfers to bypass mode
after 60 minutes or longer.
110% < load ≤ 125%: The UPS transfers to bypass mode
after 10 minutes or longer.
125% < load ≤ 150%: The UPS transfers to bypass mode
after 1 minute or longer.
When the load is greater than 150% or a short circuit
occurs, the UPS transfers to bypass mode after 200 ms or
longer.
Bypass overload capability:
The UPS runs continuously at 135% load at 30°C; the UPS
generates only alarms and uses overtemperature protection