UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
8 Technical Specifications
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
164
Item
Specifications
at 135–150% load at 30°C.
The UPS runs continuously at 125% load at 40°C; the UPS
generates only alarms and uses overtemperature protection
at 125–150% load at 40°C.
The UPS runs for 5 minutes at bypass single-phase or
three-phase load of 150%–200% at 40°C; the UPS runs for
1 minute at bypass single-phase or three-phase load greater
than 200% at 40°C.
The UPS runs for 100 ms when the load exceeds 1000%.
Table 8-9
System electrical specifications
Item
Specifications
Parallel system reliability
Redundant parallel signals
ECO in a parallel system
Supported
Number of parallel UPSs
2
Power distribution system TN, TN-C, TN-CS, TT