UPS5000-H-1200 kVA
User Manual (100 kVA Power Modules)
4 User Interface
Issue 01 (2020-07-15)
Copyright © Huawei Technologies Co., Ltd.
129
Item
Description
Default
Value
Value Range
Class 2 grid hiber. time
(d)
Specifies the hibernation time for class 2 power
grids.
6
0–15
Thres. of low batt. SOC
over dry contact(%)
If an output dry contact is set to
Low battery
SOC
and the battery SOC is lower than this
threshold, the output dry contact generates a
signal.
75
5–80
Thres. of low batt. volt.
over dry contact(V/cell)
Lead-acid battery: If
Batt. Volt. Below Threshold
is set for an output dry contact and the battery
voltage is lower than this threshold, the output dry
contact generates a signal.
1.70
1.70–2.10
Lithium battery: If
Batt. Volt. Below Threshold
is set for an output dry contact and the minimum
electrochemical cell voltage is lower than the
threshold, the output dry contact generates a
signal.
2.80
2.60–3.20
Battery String Summary
Item
Description
No. of iBOX
Number of an iBOX connected to the UPS
iBAT start No.
Start number of an iBAT connected to the iBOX
iBAT end No.
End number of an iBAT connected to the iBOX
4.2.4 Query
On the
Query
page, you can query
Historical Alarm
,
Battery Test Records
, and
Performance Data
, and perform
Export Data
.
Figure 4-47
Query
Item
Description
Historical
Alarm
Queries historical alarms of the system or components.
Battery Test
Query and export
Cap. test logs
and
Common test logs
.