Step 4
After the management module is started, use the default parameters to log in to the
management module command-line interface (CLI). The default user name is
Administrator
,
and the default password is
Admin@9000
.
Step 5
Modify the user name and password as required and record the information.
----End
Follow-up Procedure
After the configuration is complete, remove the jumper cap or other short circuit tools.
5.3.5 Configuring Basic Management Module Data
Configure basic management module data.
Prerequisites
Log in to the management module CLI.
Procedure
Step 1
Configure a management module IP address.
NOTICE
After the IP address is configured, the new IP address takes effect immediately, and you must
use the new IP address to log in again.
On the management module CLI, run one of the following commands to configure basic
management module data.
l
Setting an IPv4 address:
ipmcset -d ipaddr
-v <
ipaddr
> <
mask
> [
gateway
]
l
Setting an IPv6 address:
ipmcset -d ipaddr6
-v <
ipaddr6/prefixlen
> [
gateway6
]
describes the parameters in the
ipaddr
and
ipaddr6
command.
Table 5-6
Parameter description
Parameter
Description
Value
ipaddr
Specifies the IPv4 address of
the network port to be
configured.
The value of this parameter is in the
data type of IPv4 and in the format of
xxx.xxx.xxx.xxx.
mask
Specifies the subnet mask of
the network port to be
configured.
The value of this parameter is in the
data type of IPv4 and in the format of
xxx.xxx.xxx.xxx.
gateway
Specifies the gateway
address of the network port
to be configured.
The value of this parameter is in the
data type of IPv4 and in the format of
xxx.xxx.xxx.xxx.