FusionModule5000 Smart Modular Data Center
Installation Guide (Single-Row Aisle Containment with
2000 mm High Cabinets, ECC800)
11 Installing Cabinet Sealing Plates
Issue 01 (2019-03-05)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
167
11
Installing Cabinet Sealing Plates
Context
Cabinet sealing plates are used to seal the space under cabinets to ensure that an aisle is
airtight.
Table 11-1
Cabinet sealing plate specifications
Type
BOM Number
Description
600 mm wide cabinet
sealing plate
21242005
Applies to cabinets that are
600 mm wide and 2000 mm
high.
800 mm wide cabinet
sealing plate
21242301
Applies to cabinets that are
800 mm wide and 2000 mm
high.
300 mm wide air
conditioner sealing plate
Available in the materials
for 300 mm wide air
conditioners.
Applies to 300 mm wide air
conditioners.
Installing a 600 mm or an 800 mm Wide Cabinet Sealing Plate
Step 1
Install a sealing plate for the cabinet front door and secure it using two M5x10 tapping
screws, as shown in
Keep the edgefold of the sealing plate facing the cabinet.