Gx
Series
EN - 134
Test on RCD without integral current breaking device (with accessory RCDX10)
Differential protection type (RCD):
AC ( ), A (
), B(
) – Generali (G), Selettivi (S) e Ritardati ( )
Voltage range Phase-Earth, Phase-Neutral:
100V
265V RCD type AC and A, 190V
265V RCD type B
Rated tripping currents (I
N): 0.3A
10A
Frequency: 50/60Hz
5%
RCD without integral current breaking device tripping current - (for General RCD only)
RCD type
I
N Range
I
N
[mA]
Resolution [mA]
Accuracy
AC, A, B
300mA
I
N
1A
(0.3
1.1) I
N
0.1I
N
- 0%, +5%I
N
AC, A
1.1A
I
N
10A
Duration of RCD without integral current breaking device tripping time – TT/TN systems
x 1/2
x 1
x 2
x 5
AUTO
\ G
S G S G S G S G S G S
0.3A
1.0A
AC 999 999 999 999 999 999 200 250 50 150
310
A 999 999 999 999 999 999 200 250 50 150
310
B 999 999 999 999 999 999
310
1.1A
3.0A
AC 999 999 999 999 999 999 200 250 50 150
310
A 999 999 999 999 999 999 200 250 50 150
310
B 999 999 999 999 999 999
3.1A
6.5A
AC 999 999 999 999 999 999 200 250 50 150
310
A 999 999 999 999 999 999 200 250 50 150
310
B 999 999 999 999 999 999
6.6A
10.0A
AC 999 999 999 999 999 999 200 250
A 999 999 999 999 999 999
B
Table with duration of tripping time measurement [ms] - Resolution: 1ms, Accuracy:
(2.0
r 2digits)
Duration of RCD without integral current breaking device tripping time – IT systems (*)
x 1/2
x 1
x 2
x 5
AUTO
\ G
S G S G S G S G S G S
0.3A
3.0A
AC 999 999 999 999 999 999 200 250 50 150
310
A 999 999 999 999 999 999 200 250 50 150
B
3.1A
6.5A
AC 999 999 999 999 999 999 200 250 50 150
310
A 999 999 999 999 999 999 200 250 50 150
B
6.6A
10.0A
AC 999 999 999 999 999 999 200 250
A 999 999 999 999 999 999 200 250
B
Table with duration of tripping time measurement [ms] - Resolution: 1ms, Accuracy:
(2.0
r 2digits)
(*) Selection RCD type A only available for Norvay country
Overall earth resistance without RCD tripping (NoTrip )
Voltage range Phase-Earth, Phase-Neutral:
100
265V, Frequency: 50/60Hz
5%
Global earth resistance in systems with Neutral
Range [
] Resolution
[
]
Accuracy (*)
0.01
9.99
0.01
-
(5
rdg +N/10)
10.0
199.9
0.1
-
(5
rdg +N)
200
1999
1
-
(5
rdg + 3N)
(*) If I
N
<30mA, test current = I
N
/2 and N[
]=30/I
N
; if I
N
≥
30mA, test current <15mA and N=1
Global earth resistance in systems without Neutral
Range [
] Resolution
[
]
Accuracy
1
1999
1
-
(5
rdg +N)
(*) if I
N
<30mA, test current = I
N
/2 and N[
]=(10x30)/I
N
; If I
N
≥
30mA, test current I
N
/2 and N[
]=(3x30)/I
N