Gx
Series
EN - 31
x½, x1, x2, x5 modes
6.3.3.
9. Press the
GO/STOP
key
for few seconds
on the
instrument or the
START
key on the remote lead. The
instrument will start the measurement.
The screen to the side (concerning multiplier
x1
) is
shown on the display when the hourglass icon indicates
the performance of the test.
10 At the end of the test with multiplier
x1/2
,
x1, x2
or
x5
if
the tripping time, for
molded case type STD
, is as
listed in Table 6
the instrument shows the
symbol to signal that the
test has been completed successfully, and displays a
screen similar to the one reported here to the side.
Press the
SAVE
button or touch the
icon to save
the measurement (see § 7.1).
11 At the end of the test, for
molded case type STD
, if the
tripping time of a test does not comply with what is
indicated in Table 6the instrument shows the
symbol to signal that the test has not been completed
successfully, and displays a screen similar to the one
reported here to the side.
Press the
SAVE
button or touch the
icon to save
the measurement (see § 7.1).
Mode x1 – Test on RCDs with delay time
6.3.4.
9. At the end of the test, if the measured tripping time is
within the interval: [
limit delay = set delay time +
value indicated in Table 6]
the instrument displays
the
symbol to indicate the positive outcome of the
test and displays a screen like the one to the side.
Press the
SAVE
button or touch the
icon to save
the measurement (see § 7.1).
10 At the end of the test, if the measured tripping time is
external the interval: [
limit delay = set delay time +
value indicated in Table 6]
the instrument displays
the
symbol to indicate the negative outcome of the
test and displays a screen like the one to the side.
Press the
SAVE
button or touch the
icon to save
the measurement (see § 7.1)