Gx
Series
EN - 132
11. TECHNICAL
SPECIFICATIONS
Accuracy is calculated as: ±[%r (no. of digits) * resolution] at 23°C, <80%RH.
Refer to the Table 1 for the correspondence between models and availbale features
11.1. TECHNICAL
CHARACTERISTICS
AC TRMS voltage
Range [V]
Resolution [V]
Accuracy
15
460
1
(3%rdg + 2digits)
Frequency
Range [Hz]
Resolution [Hz]
Accuracy
47.0
63.6
0.1
(0.1%1digit)
Continuity of protective conductor (RPE)
Range [
] Resolution
[
]
Accuracy (*)
0.01
99.99
0.01
(5.0
r 3digits)
100
1999
1
(10.0
rdg + 5digits)
(*) after calibration of measuring cables
Test current: >200mA DC up to 2
(cables included) ; Test current resolution: 1mA ; Open-circuit voltage: 4 < V0 < 24V
Insulation resistance (M
)
Test voltage [V]
Range [M
] Resolution
[M
]
Accuracy
50
0.01
9.99
0.01
(2.0
r 2digits)
10.0
49.9
0.1
50.0
99.9
(5.0
r 2digits)
100
0.01
9.99
0.01
(2.0
r 2digits)
10.0
99.9
0.1
100.0
199.9
(5.0
r 2digits)
250
0.01
9.99
0.01
(2.0
r 2digits)
10.0
99.9
0.1
100
499
1
(5.0
r 2digits)
500
0.01
9.99
0.01
(2.0
r 2digits)
10.0
199.9
0.1
200
499
1
500
999
(5.0
r 2digits)
1000
0.01
9.99
0.01
(2.0
r 2digits)
10.0
199.9
0.1
200
999
1
1000
1999
(5.0
r 2digits)
Open-circuit voltage
rated test voltage -0% +10%
Rated measuring current:
>1mA with 1k
x Vnom (50V, 100V, 250V, 1000V), >2.2mA with 230k
@ 500V
Short-circuit current
<6.0mA for each test voltage
Safety protection:
error message for input voltage > 10V
Line/Loop impedance (Phase-Phase, Phase-Neutral, Phase-Earth)
Range [
] Resolution
[
]
Accuracy (*)
0.01
9.99
0.01
(5%rdg + 3digits)
10.0
199.9
0.1
(*) 0.1 m
in range 0.1
199.9 m
(by using the optional accessory IMP57)
Maximum test current:
5.81A (at 265V); 10.10A (at 457V)
Phase-Neutral/Phase-Phase Test voltage: (100V
265V) / (100V
460V); 50/60Hz ±5%
Protection types:
MCB (B, C, D, K), Fuse (aM, gG, BS882-2,BS88-3, BS3036, BS1362)
Insulating sheath materials:
PVC, Butyl rubber, EPR, XLPE
First fault current – IT systems
Range [mA]
Resolution [mA]
Accuracy
0.1
0.9
0.1
(5
1digit)
1
999
1
(5
r 3digits)
Limit contact voltage (ULIM) : 25V, 50V