Gx
Series
EN - 102
2.
Touch the icon
to zero the value into the “FS” field
and use the virtual keyboard to set the full scale of the
used transducer clamp. This value is within the range:
1A
3000A
Touch the right bottom icon to set the type of
measurement. The display shows the following screen
3. Move the reference of the slide bar to select the
followed available options:
1Ø
Measurement on Single phase plant
3Ø
Measurement on Three phase balanced
Confirm the choice by going back to the initial
measurement screen
4. Insert the blue and black connectors into the corresponding B4 and B1 input terminals of
the instrument. Insert the remaining free end of the cables in the corresponding
crocodiles or tips. Connect crocodiles or test leads to the phase P and N according to
Fig. 36 for the measurement of the voltage in Single phase plant or at L1 and L2 phase
according to Fig. 37 for the measurement of voltage in a Three phase balanced plant.
Connect the clamp to
In1
input of the instrument and to the phase conductor for Single
phase or to the L3 phase for Three phase balanced systems. The arrow on the clamp
must follow the direction in which the current normally flows from the generator to the
load, as shown in Fig. 36 and Fig. 37
5. The screen to the side shows the real time values of
electrical parameters in a Single phase plant. For the
meaning of the parameters refer to § 13.15. The
symbols “
” and “
” show the type Inductive or
Capacitive of the load respectively.
6. The screen to the side shows the real time values of
electrical parameters in a Three phase balanced plant.
For the meaning of the parameters refer to § 13.15.
The symbols “
” and “ ” show the type Inductive or
Capacitive of the load respectively.
Press the
SAVE
button or touch the
icon to save
the measurement (see § 7.1)